Calculation of Quantities


Calculation of Quantities

How many Air vent is required to my site?

Calculating the Number of Turbines Required at a Site.

Measurement of the site : First note down the Length, Breadth & Height of the Site in Feet.

Then Calculate the Total Volume.

V1= L X W X h1
V2= L X W X (h2-h1) / 4
V= V1 + V2

Total Volume X Air Change / CFM X 60 = Total No of Units.

Air Change = No of Times the Inside air of the building to be Changed by Fresh Air

Exhaust Capacity of our vents at below mentioned environment conditions.



Table B : Performance Data

Type of Building

Air Changes Rate/Hr.

Ware House

4-6

 Textile Mill / Auditorium

4-12

 Factories ( Light) / Hall

6-12

Paper Mill / Brewery / Oil Mill / Packaging Room

8-30

 Engine room / Painting Shop / Laundry /Plastic Factory

10-30

Heavy Factory / Transformer room

 12-30

Paint Shop / boiler Room

15-60

 


Specifications

Model No.

Stack (Height Ft)

Exhaust Capacity in CFM

SI-500

10

939

1000

1102

1436

1498

1600

1792

1854

1958

SI-700

20

1005

1084

1216

1503

1582

1714

1859

1938

2070

SI-800

30

1058

1154

1314

1556

1652

1812

1915

2010

2168

  40

1107

1216

1398

1605

1714

1896

1961

2070

2252

 

For Example : There is a building which is 120 Ft length, 64 Ft width and 25 Ft height. The difference in temperature between indoor and outdoor is 10°C, and the wind speed is 9.6KM hr. Moreover the ventilating times of the casting factory according to the standard material is between 10 to 30 times per hour. So the ventilating cube is (100×75×25) ×10 times hr = 1920000cube hr.

 

1920000cbm/hr / 1714cbmX60 according to the different model 500/700/788 = 18.66(units)

 

So we’d better install 19 units’ ventilators for the workshop.